  • solenoid releasing module

    Download Catalogue

    Standard Features

    Solenoid output with supervision for open and short circuit conditions. Check on supervised status occurs upon receipt of an A-D command

    Output relay rated to supply 2A @ 30 VDC for the solenoid load

    Addressable FET switch used to control output for extra security in releasing functions

    Activation pulse time from 5-30 minutes in 5 minute intervals

    Visible Bi-colored LED is software controlled and is Red when the Module is active and Green when normal. The LED can be latched on when activated

    Programmed with DCP expansion mode commands or with a handheld programmer 

     

    Application

    This module will be connected to a SLC loop on an Elite FACP with Networked Releasing. The VF6006 will provide
    a supervised 24 VDC output to a re alarm releasing solenoid or squib agent (reverse current relay) release supervision circuit.

    There are separate wiring terminals provided for both the Solenoid and Agent Release Module (ARM) devices. Although there are two sets of terminals, this module can only be used for one type at a time. The ARM end-of-line (EOL) resistor must be removed when used with a solenoid. A panel command allows the user to choose which type of device is being controlled and supervised. In

    the event of an alarm condition, the module will be activated to supply up
    to 2 amps of current to the solenoid or ARM devices. The solenoid activation time is programmable at the control panel. Solenoid activating pulse time can be programmed from 5-30 minutes in
    5 minute intervals. The output can also be latched on until commanded to be turned o by the control panel.

    Operation

    The VF6006 Solenoid Releasing Module is designed to control a single hazard when connected to the Elite SLC loop. Multiple Releasing Modules may be attached to the loop, controlling di erent areas, all triggered by the same event.

    Alarm events may be on di erent panels in a networked system and the NAC outputs may also be used for releasing. Events that trigger a NAC channel and Releasing Module all have the same output command. 
    Tham khảo các thiết bị tương tự: Cảm biến khói, Đầu dò khói, đầu báo khói, báo khói
     

    Technical Speci cations

    Absolute Max. Applied Voltage:

    S, SC: 41 VDC Aux+, Aux-: 26 VDC

    Supply Voltage Nominal:

    S, SC: 33 VDC Aux+, Aux-: 24 VDC

    Normal Current Consumption (S, SC): 220μA

    Max. Current Consumption (S, SC): 300μA

    Normal AUX+, AUX- Consumption: 1.2mA

    Max. Output Current to SOL+, SOL-: 2A @ 30VDC

    End Of Line Device: 2.7K Ohms

    Dimensions: 4.2”W x 4.7”H x 0.85”D

    Ambient Temperature: 32o F to 120o F

    Humidity: 90 % RH, Non-condensing

    Mounting: 4” Square electrical box