Sản phẩm
-
solenoid releasing module
Standard Features
Solenoid output with supervision for open and short circuit conditions. Check on supervised status occurs upon receipt of an A-D command
Output relay rated to supply 2A @ 30 VDC for the solenoid load
Addressable FET switch used to control output for extra security in releasing functions
Activation pulse time from 5-30 minutes in 5 minute intervals
Visible Bi-colored LED is software controlled and is Red when the Module is active and Green when normal. The LED can be latched on when activated
Programmed with DCP expansion mode commands or with a handheld programmer
Application
This module will be connected to a SLC loop on an Elite FACP with Networked Releasing. The VF6006 will provide
a supervised 24 VDC output to a re alarm releasing solenoid or squib agent (reverse current relay) release supervision circuit.There are separate wiring terminals provided for both the Solenoid and Agent Release Module (ARM) devices. Although there are two sets of terminals, this module can only be used for one type at a time. The ARM end-of-line (EOL) resistor must be removed when used with a solenoid. A panel command allows the user to choose which type of device is being controlled and supervised. In
the event of an alarm condition, the module will be activated to supply up
to 2 amps of current to the solenoid or ARM devices. The solenoid activation time is programmable at the control panel. Solenoid activating pulse time can be programmed from 5-30 minutes in
5 minute intervals. The output can also be latched on until commanded to be turned o by the control panel.Operation
The VF6006 Solenoid Releasing Module is designed to control a single hazard when connected to the Elite SLC loop. Multiple Releasing Modules may be attached to the loop, controlling di erent areas, all triggered by the same event.
Alarm events may be on di erent panels in a networked system and the NAC outputs may also be used for releasing. Events that trigger a NAC channel and Releasing Module all have the same output command.
Tham khảo các thiết bị tương tự: Cảm biến khói, Đầu dò khói, đầu báo khói, báo khói
Technical Speci cations
Absolute Max. Applied Voltage:
S, SC: 41 VDC Aux+, Aux-: 26 VDC
Supply Voltage Nominal:
S, SC: 33 VDC Aux+, Aux-: 24 VDC
Normal Current Consumption (S, SC): 220μA
Max. Current Consumption (S, SC): 300μA
Normal AUX+, AUX- Consumption: 1.2mA
Max. Output Current to SOL+, SOL-: 2A @ 30VDC
End Of Line Device: 2.7K Ohms
Dimensions: 4.2”W x 4.7”H x 0.85”D
Ambient Temperature: 32o F to 120o F
Humidity: 90 % RH, Non-condensing
Mounting: 4” Square electrical box